Description
The Best Value in Power Quality Monitoring
Power from the Phase Feature; Power the Instrument from the Circuit Being Measured, or Another Source
Tests 16/25Hz and 50/60Hz
Powered by the Phase Being Measured!
Wired Ethernet Communications
Bluetooth Optional
GPS Optional (Factory installed only)
Made in the USA

The Dranetz HDPQ Visa SP has the same measurement and communications capabilities as the Dranetz HDPQ Visa, but is housed in an IP65 enclosure without an LCD display, and can also be powered by the circuit being measured. The IP65 enclosure of the Dranetz HDPQ Visa SP greatly expands the applications of the Dranetz HDPQ Visa into outdoor and harsh environments, along with other applications where an LCD display is undesirable.
The HDPQ Visa SP enables users to review data and change settings remotely from virtually any smartphone, tablet and mobile device, as well as with traditional PC and MAC laptops and desktops. Just hook up the instrument, close the cabinets to the ‘safe’ environment, and use either the VNC interface along with our Dran-View 7 software, or our Dranetz HDPQ Apple or Android Apps via Ethernet for remote control from anywhere with connectivity to the instrument.
Dranetz HDPQ Visa SP – Precision
• High Definition PQ & Energy Monitoring – 1000Vrms, AC/DC, 512 samples/cycle
• Eight channels, 4 voltage & 4 current
• Advanced PQ – IEC 61000-4-30 Class A & IEEE 1159 compliant
• Harmonics – IEC 61000-4-7, IEEE 519 (2014)
• Transient capabilities – V & I waveshape triggers. Well beyond standards requirements
• 100 cycle pre/post trigger buffer
• EN 50160 Ed 3
• Motor AnswerModule®
Dranetz HDPQ Visa SP – Communications
• Ethernet, USB, Bluetooth – Optional
• VNC for full remote control from Dran-View 7 or a 3rd party App
• Apple & Android apps with real time metering and alarm Dashboard
Dranetz HDPQ Visa SP – Safe & Rugged
• Arc Flash Safety
• UL/cUL listed and CE approved
• Rugged enclosure with an easy to grip, shock absorbing, non-conductive boot (Dranetz HDPQ Visa only)
• Power supply cable retainer and wire management (Dranetz HDPQ Visa only)
• IP65 enclosure for harsh and outdoor environments (Dranetz HDPQ Visa SP only)
• Drop tested to 6’ (Dranetz HDPQ Visa only)
• Automatic circuit detection and feedback on proper connection of the instrument
Dranetz HDPQ Visa SP – User Interface
• Automatic setups – PQ, Demand and Energy
• Tablet-like GUI that is icon driven, has taskbar shortcuts, and a Dashboard (only available remotely)
Dranetz HDPQ SP – Productivity
• Mini-Report – Screen snapshots, XML file. Easily uploaded and emailed!
• PQ & Energy Dashboard’s for real time alarming
• Dran-View 7 power quality analysis software
• Rescue kit – Part of Dran-View 7. Correct problems with wiring, CT orientation, time errors and more
• Post processing – Part of Dran-View 7. Compute harmonics and other parameters from the waveforms recorded by the instrument
Dranetz HDPQ Visa SP – Measured Parameters
(4) Differential Voltage: 16 bit resolution
- 0-1000Vrms, AC/DC, +/- 0.1% reading +/- 0.05% FS
- IEC 61000-4-30 Class A: 60-1000Vrms, ±0.1 % of Udin, range of 10% ~ 150% of Udin
- Transients – 0-1414Vpk, +/- .2% of Udin
(4) Current: 512 samples/cycle, 16 bit resolution
- Range (rms) probe dependent, AC/DC, +/- 0.1% reading +/- 0.05% FS
- Transients – Range probe dependent
Frequency: 10 sec window
- 16-25Hz, 42.5-69Hz, +/- 0.01Hz
Calculated Parameters
Power/Energy – 1 Second sampling
Real Power (W) – P: meets 0.2S requirements, range probe dependent
Apparent Power (VA) – S: meets 0.2S requirements, range probe dependent
Reactive Power (var) – Q: meets 0.2S requirements, range probe dependent
Power Factor (W/VA) -”true” -1 to 0 to 1
Displacement PF -1 to 0 to 1
Demand (in W): meets 0.2S requirements, range probe dependent
Energy (in Wh): meets 0.2S requirements, range probe dependent
Distortion – 200ms, 3 sec, 10 min windows
Vthd: 0-100%, +/- 5% for V>=1% Vnom,
V Ind Harm: DC, 2-127, +/- 5% for V>=1% Vnom
Ithd: 0-100%, +/- 5% for I>=1% Inom,
I Ind Harm: DC, 2-63, +/- 5% for I>=1% Inom
Misc.
Pst – 10 minutes: 0.2-10, +/- 0.05 @ Pst=1
Plt – 2 hours: 0.2-10, +/- 0.05 @ Pst=1
Standards Compliance
Power Quality
IEC 61000-4-30 Class A: Edition 2 (2008)
IEEE 1159: 2009
Power
IEEE 1459: 2000
Harmonics
IEC 61000-4-7 Class 1: Edition 2 (2008)
IEEE 519: 2014
Voltage Flicker
IEC 61000-4-15: Edition 2 (2010)
IEEE 1453: 2011
Compliance/Testing
EN 50160: 2010
General Specifications
Dranetz HDPQ Visa SP (IP65)
- Size: (11″w x 6.5″h x 2.5″d), (27.9cm x 16.5cm x 6.4cm)
- Weight: 3.8lbs, 1.72kg
- Operating temperature: -10 to 50 deg C (14 to 122 deg F)
- Storage temperature: -40 to 85 deg C (-40 to 185 deg F)
- Humidity: 10-90 non condensing
- Power Supply: 90-600VAC/500VDC (50/60Hz). Powered by the phase being measured, or other source
Clock accuracy and resolution
- Internal: +/- 1 sec/day at 25 deg C
- NTP: +/-10 msec
- GPS: +/-1 msec
Battery capacity and charge time:
- Dranetz HDPQ Visa SP: 30 minutes run time on full charge, 3 hours charge time
Memory size: 4GB
Communications:
Ethernet
Bluetooth (optional)
USB On the Go (OTG)
VNC remote control
Android & Apple Apps
Ease of Use Features
Automatic Setups – Start monitoring in seconds!
Pre-programmed monitoring modes – Pre-configured setups for various applications
Dashboards – Power Quality, Demand & Energy – Immediately know when events have been recorded
Simultaneous Power Quality, Demand & Energy monitoring
Mini-Report – Take screen snapshots that can be uploaded to your computer and included in reports, attached to emails, etc.
Power the instrument from the circuit being measured, or another source (SP Only)